A research poster from the School of Emergent Priorities weighs the calcite scraped from the plate heat exchangers of twelve apartment buildings' shared hot-water plants at 36 annual services, all on one hard municipal supply. Deposition rates six-fold apart track the calcite saturation index at the plate wall (R² = 0.95) rather than at the storage setpoint each owners corporation resolves (R² = 0.12), doubling with about every 6 °C of wall temperature, and five mid-study setpoint changes left deposition within each building's own spread.